Indoor Room Temperature Sensor Open or Short Circuit

Home Appliance Error Codes Gree Split AC

Severity Medium Do not ignore it; it may get worse and cost more.
Can you still use it? With care until repaired
Who can fix it? Needs a technician
Typical repair time 30 minutes – 2 hours
Cost level High In the Saudi market: SAR 80–1,200 (≈ USD 21–320)

What it means

This code appears on Gree split air conditioners when the control board reads an impossible value from the indoor room temperature sensor, meaning the sensor or its circuit is open or shorted. This sensor measures the air entering the indoor unit; without it the unit cannot tell when the room has reached the set temperature, so it stops cooling or runs erratically depending on the model. The same code can mean something else on other brands.

Models covered: Gree split (wall-mounted) air conditioners, mainly inverter models; the code shows on the indoor unit display. Older non-inverter models may show fewer codes.

Symptoms3

  • The code appears at start-up or after a few minutes.
  • The unit does not cool, or cools without cycling off at the set temperature.
  • The room ends up colder or warmer than the setting.

Possible causes5

  • Loose or corroded sensor connector on the indoor control board, which is the most common cause.
  • Failed sensor (thermistor) from moisture or age.
  • Broken or chafed sensor wire from rubbing, rodents or heat.
  • Water leaking inside the indoor unit onto the sensor or connector.
  • Faulty sensor input circuit on the indoor control board, which is less common.

How to diagnose5

  1. Switch off at the breaker for a few minutes and restart to see if the code is permanent.
  2. The technician checks the sensor connector on the indoor control board and reseats it firmly.
  3. The technician removes the sensor, measures its resistance and compares it with the Gree resistance table at a known temperature.
  4. The technician inspects the wire along its length for breaks or chafing.
  5. If the sensor and wire are fine, the technician tests the board with a known-good sensor.

How to fix5

  1. Clean and firmly reseat the connector.
  2. Repair and insulate the damaged wire.
  3. Replace the sensor with the correct part for the model and fit it in its original position.
  4. Replace the indoor control board only if its input circuit is proven faulty.
  5. Run the unit and confirm the code is gone and cooling is normal.

Repair cost

Prices for
Cost levelHigh

In the Saudi market: SAR 80–1,200 (≈ USD 21–320)

Our prices come from the Saudi market, converted at a fixed rate (SAR 3.75 per USD). Prices in your country may differ a lot, so we show the cost level.

A connector clean or a new sensor is usually enough and cheap; the cost only rises if the control board has to be replaced.

Prices are rough estimates including the part and the technician’s fee, and vary with brand, model and part source.
Prices last updated: September 2026

Frequently asked questions

Where is the room temperature sensor?

In the indoor unit near the air intake in front of the evaporator, wired to the indoor board by a short lead. Reaching it means removing the cover with the power off.

Can I use the AC until the technician comes?

Some models run in a limited way, but temperature control will not be accurate. It is usually a cheap fix, so repair it soon.