A1

Discharge Temperature Protection

Home Appliance Error Codes Fujitsu Split AC

Severity High Get it checked soon and avoid long use.
Can you still use it? No, unplug it
Who can fix it? Needs a technician
Typical repair time 1 hour – 8 hours
Typical cost SAR 200 to 5,000

What it means

This code appears on Fujitsu General split and ducted units on the wired remote or indoor display; older models show it as a number of indicator lamp blinks instead of a number. It means the discharge temperature sensor measured a truly high temperature of the gas leaving the compressor, above the protection limit, so the unit stopped the compressor until it cools. The most common causes are low refrigerant or a restriction in the circuit, and the unit may lock out if the code repeats. The same number can mean something different on other brands.

Models covered: Fujitsu General (Fujitsu, O General) split and ducted units that show a two-digit error code on the wired remote or indoor display; older models show errors as lamp blink counts instead.

Symptoms4

  • Cooling fades gradually, then the compressor stops.
  • The outdoor unit starts and stops repeatedly.
  • Intense heat around the compressor and discharge pipe.
  • Sometimes ice on the pipe at the outdoor unit.

Possible causes5

  • Low refrigerant from a leak, so less cool gas returns to the compressor.
  • A blocked electronic expansion valve, filter or pipe.
  • Service valves left partly closed after installation or relocation.
  • A dirty outdoor coil or poor airflow in extreme heat.
  • A falsely high reading from the discharge sensor (less common).

How to diagnose5

  1. Switch off at the breaker, let the unit cool, and clear the area around the outdoor unit.
  2. Recall whether cooling faded gradually, a typical sign of low refrigerant.
  3. The technician measures refrigerant pressure and discharge pipe temperature against the manufacturer specification.
  4. The technician looks for a leak, confirms the service valves are open and checks the expansion valve.
  5. The technician compares the discharge sensor reading with the actual pipe temperature to rule out a sensor error.

How to fix5

  1. Fully open the service valves if they were partly closed.
  2. Wash the outdoor coil and improve airflow around the outdoor unit.
  3. Repair the leak and recharge refrigerant by weight; this is work for a licensed technician.
  4. Replace a blocked expansion valve or filter, or the sensor if proven wrong.
  5. Replace the compressor at an authorized service center if it is damaged, then confirm the code does not return.

Repair cost

In Saudi riyals; the highlighted part is the expected range for this fault.

The cost is low for a closed valve or dirt, moderate for leak repair, and reaches the top of the range if the compressor was damaged by running hot for long.

Prices are rough estimates including the part and the technician’s fee, and vary with brand, model and part source.
Prices last updated: September 2026

Frequently asked questions

Will a refrigerant top-up fix it?

Only after the leak is repaired. Topping up without a repair brings the code back and risks the compressor.

What is the difference between A1 and code 71?

Code 71 means the sensor itself has failed. A1 means the measured temperature is really high, and the cause must be found in the refrigerant circuit.