Trip Detection (Overcurrent)
What it means
This code appears on Fujitsu General split and ducted units on the wired remote or indoor display; older models show it as a number of indicator lamp blinks instead of a number. It means the protection circuit on the inverter board detected a sudden overcurrent in the compressor drive and cut operation at once. It is one of the most serious outdoor codes because the cause may be a short in the compressor or the power module (IPM). The same number can mean something different on other brands.
Models covered: Fujitsu General (Fujitsu, O General) split and ducted units that show a two-digit error code on the wired remote or indoor display; older models show errors as lamp blink counts instead.
Symptoms4
- The unit stops suddenly moments after the compressor starts.
- The breaker may trip at the same time.
- A crackling sound or burning smell from the outdoor unit in some cases.
- The code returns immediately after a restart.
Possible causes5
- A faulty power module (IPM) or inverter board.
- A short or weak insulation in the compressor windings.
- A mechanically seized compressor drawing high current at start.
- Burnt compressor wires or wires touching the frame.
- Deep voltage dips or sudden surges.
How to diagnose5
- Switch off at the breaker and do not restart more than once.
- Tell the technician whether the breaker tripped or there was a burning smell.
- After discharging the board, the technician checks compressor wires and terminals.
- The technician measures winding resistance and insulation to the frame against the manufacturer specification.
- The technician tests the power module and inverter board output using the service manual.
How to fix5
- Keep the unit off and call a technician qualified on inverter boards.
- Repair or replace burnt compressor wiring.
- Replace the inverter board at an authorized service center if the power module has failed.
- Replace the compressor first if it is shorted or seized, before fitting a new board.
- Fit a voltage protector, then confirm the code does not return.
Repair cost
In Saudi riyals; the highlighted part is the expected range for this fault.
The cost is low for wiring or voltage problems, much higher for a new inverter board, and reaches the top of the range when the inverter compressor must be replaced.
Prices are rough estimates including the part and the technician’s fee, and vary with brand, model and part source.
Prices last updated: September 2026
Frequently asked questions
Why not keep restarting the unit?
Each attempt with overcurrent can further damage the power module or compressor, turning a small fault into a costly repair.
Is it the compressor or the board?
Measuring the compressor windings and insulation decides it. A shorted compressor must be replaced before the board, or the new board will fail.
Was this explanation helpful?
Tap the stars to rate; you can change it later.
What was wrong? (optional)
This guide is for information only and does not replace an inspection by a qualified technician. If the fault involves brakes, steering, engine temperature, electrics or refrigerant, do not attempt the repair yourself.
Report a mistake
Spotted something inaccurate? Tell us and we will review and correct it.
Report received — thank you
This is your private tracking link. It shows the status and our reply as soon as it is posted.
The link is saved in this browser only.