Discharge Temperature Sensor Error
What it means
This code appears on Toshiba residential split air conditioners when the fault code is read with the remote check function. It means the discharge temperature thermistor (TD) on the compressor outlet line in the outdoor unit is open or shorted. The outdoor unit stops the compressor because it cannot protect it from overheating without this reading. The same code can mean something else on other brands, and Toshiba commercial units use different codes.
Models covered: Toshiba residential split air conditioners (RAC) that show a two-character check code through the remote check function; Toshiba commercial units use different codes.
Symptoms4
- The outdoor unit stops and cooling is lost.
- The indoor unit lamps blink and code 19 is found on check.
- The fault returns right after restart or within minutes.
- The fault appears after the outdoor unit was washed or serviced.
Possible causes5
- A loose or unplugged sensor connector on the outdoor board.
- A thermistor damaged by repeated high temperature on the discharge line.
- A sensor lead burned by the hot pipe, or cut.
- Water or corrosion in the connector after washing.
- A fault in the sensor input circuit on the outdoor board.
How to diagnose5
- Read the code with the remote check function: press and hold the check button, then step through the codes with the timer button until the indoor unit beeps continuously; the code shown then is the fault. Steps vary slightly by remote, so follow the owner's manual.
- Switch off at the breaker for several minutes, restart and note when the fault returns.
- Switch off at the breaker before opening any panel; the outdoor unit and its inverter board keep a dangerous charge for a while after switch-off.
- The technician checks the sensor connector on the board and traces the lead along the discharge line for burns or breaks.
- The technician measures the sensor resistance against the manufacturer table, then checks the board if the sensor is good.
How to fix5
- Dry, clean and reseat the connector.
- Repair the lead and secure it away from hot pipes.
- Replace the discharge thermistor with the correct part and fix it firmly to the pipe.
- Replace the outdoor control board if its circuit is proven faulty.
- Run the unit and confirm a sensible discharge temperature reading and no code.
Repair cost
In Saudi riyals; the highlighted part is the expected range for this fault.
The cost is low for a new thermistor or lead repair, and rises sharply if the outdoor unit needs a new control board.
Prices are rough estimates including the part and the technician’s fee, and vary with brand, model and part source.
Prices last updated: September 2026
Frequently asked questions
How is 19 different from 1E?
Code 19 means the discharge sensor or its lead has failed, while 1E means the sensor works and is actually reading a high discharge temperature.
Can the unit run without the sensor?
No. The sensor protects the compressor from overheating, and bypassing it can destroy the compressor.
Is the repair expensive?
Usually not. The thermistor is fairly cheap; the cost only rises if the outdoor board is at fault.
Was this explanation helpful?
Tap the stars to rate; you can change it later.
What was wrong? (optional)
This guide is for information only and does not replace an inspection by a qualified technician. If the fault involves brakes, steering, engine temperature, electrics or refrigerant, do not attempt the repair yourself.
Report a mistake
Spotted something inaccurate? Tell us and we will review and correct it.