Compressor Overload (OL Activated)
What it means
This code appears on Daikin split, ducted and cassette air conditioners and means the compressor overload (OL) protection has tripped because the compressor ran too hot or drew too much current. The unit stops the compressor until it cools and then retries; a repeating code signals a real problem. The same code can mean something else on other brands.
Models covered: Daikin split air conditioners and Daikin ducted/cassette (SkyAir) units, which share the same error code system; the code shows on the wired remote or via the wireless remote check function.
Symptoms4
- The unit runs for a while, then the compressor stops and E5 appears.
- Weak cooling and a very hot outdoor unit.
- Trips happen more often in the hottest hours.
- Sometimes an unusual noise from the compressor.
Possible causes6
- Low refrigerant charge, so the compressor overheats from too little returning gas.
- A dirty condenser or weak outdoor fan raising pressure and temperature.
- A service valve not fully open or a restriction in the circuit.
- An electronic expansion valve fault.
- Low or unstable supply voltage.
- Internal compressor wear, or a fault in its protector or wiring.
How to diagnose5
- Switch the unit off and let it cool, then make sure the outdoor unit is clean with clear airflow around it.
- Check that the home supply voltage is stable.
- A technician measures pressures and discharge line temperature against Daikin specifications to confirm the charge.
- The technician checks the service valves and the electronic expansion valve.
- The technician checks the compressor wiring, windings and protector per the service manual after discharging the inverter board.
How to fix5
- Wash the outdoor unit and repair a weak outdoor fan.
- Fit a voltage protector or fix a low voltage supply.
- A licensed technician repairs any leak and recharges to the correct amount.
- Replace the electronic expansion valve or repair compressor wiring as the tests show.
- Replace the compressor if it has an internal fault, then run the unit for hours and confirm the code does not return.
Repair cost
In Saudi riyals; the highlighted part is the expected range for this fault.
The cost is low when a dirty outdoor unit or voltage is the cause, higher with a leak repair, and highest when a new inverter compressor is needed.
Prices are rough estimates including the part and the technician’s fee, and vary with brand, model and part source.
Prices last updated: September 2026
Frequently asked questions
Does E5 mean the compressor is ruined?
Not necessarily. Often the compressor is fine but overheats because of low refrigerant or a dirty condenser. Those causes must be ruled out before blaming the compressor.
Should I restart the unit every time the code shows?
Do not keep doing that. Each restart with the same fault heats the compressor further and raises the risk of damage, so have a technician check it.
Was this explanation helpful?
Tap the stars to rate; you can change it later.
What was wrong? (optional)
This guide is for information only and does not replace an inspection by a qualified technician. If the fault involves brakes, steering, engine temperature, electrics or refrigerant, do not attempt the repair yourself.
Report a mistake
Spotted something inaccurate? Tell us and we will review and correct it.
Report received — thank you
This is your private tracking link. It shows the status and our reply as soon as it is posted.
The link is saved in this browser only.